GET A QUOTE

Fire Alarm System (EN54)

Fire alarm control panel

SEC1000

Product features

Up to 120 addresses on one loop.

The loop supports class A and Class B types.

An easy to read, 4.3"color screen LCD with a resolution of 480×272.

Zone indicators for 16 zones gives a quick indication of the location of an alarm.

Record capacity of 1000 historical events for each of historical fire, historical fault and historical operation.

An independently programmable conventional sounder circuit output.

Integral power supply and battery.

Flexible and intuitive cause and effect programming on front panel.

Zone test, point test and module start/stop testing facilitate the commissioning.

U-disk interface makes the load and save of configuration or historical data convenient for system commissioning and maintenance.

Hierarchy management with three access levels.

Anti-tamper protection by a key lock.

CAN bus for interconnection of up to 20 FACPs.

Read more detail


  • The purpose of the SEC1000 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 with qualities of simple installation, operation and easy maintenance. 


  • The SEC1000 panel is an addressable fire detection panel with 1 loop of 120 addressable points and expansion capabilities. It is compatible with other peripherals made by Sanjiang with its own protocol.

Technical Parameters:
Mains supply110V/230VAC (-15%, +10%). 50Hz/60Hz.
Mains fuseT3.15AL250V
Operating voltage20 ~ 28VDC
Recommended mains cableStandard/black mains cable, cable size 0.75mm2
Power ratingImin=0.45A; Imax.a=1.15A; Imax.b=1.65A
Max. battery supply current3A (when the Mains is disconnected)
Max. charging current1A
Battery capacity, type and recommended modelNP7-12 for 7Ah VRLA(Yuasa)
Max. internal resistance of battery
Battery fuseF6AL250V
Quiescent current (full loaded)< 0.4A
S.C.Out (+, -)Output voltage: 20 ~ 28VDC
Max. output current: 800mA, 1A S.C.Out+24VK in total
End of line resistor: 47K ohm 0.25W
Recommended type of cable: Plain unscreened cable, 1.5mm2
Cable diameter:1mm2 ~ 2.5mm2
Transmission distance:≤1500m
F.A. Out (+, -)Output voltage: 20 ~ 28VDC
Max. output current: 100mA
End of line resistor: 47K ohm 0.25W
Recommended type of cable: Plain unscreened cable, 1.5mm2
Cable diameter: 1mm2 ~ 2.5mm2
Transmission distance: ≤1500m
FAULT OUT(COM, NO)Contact capacity: 30VDC@2A, 125VAC@0.5A
24VK (+, -)Recommended type of cable: Plain unscreened cable, 1.5mm2
Cable diameter: 1mm2 ~ 2.5mm2
Output voltage: 20 ~ 28VDC
Max. output current: 500mA, 1A S.C.Out+24VK in total
Recommended type of cable: Plain unscreened cable, 1.5mm2
Cable diameter: 1mm2 ~ 2.5mm2
LOOP OUT (+, -)
LOOP IN (+, -)
Output voltage:18.5 ~ 28VDC, pulse
Max. output current: 500mA
Loop type: Class A and Class B
Recommended type of cable: Unscreened twisted-pair, 1.5mm2
Max. Loop length: 2000m(Class A)
Cable diameter: 1mm2 ~ 2.5mm2
RS-485Transmission rate: 9600 bps
Recommended type of cable: Unscreened twisted-pair, 1mm2
Transmission distance: ≤1000m
Cable diameter: 1mm2 ~2.5mm2
CANMax. number of panels: 20
Transmission rate: Optional: 10K, 20K, 50K and 100K bps
Recommended type of cable: Unscreened twisted-pair, 1mm2
Transmission distance: ≤1000m
Cable diameter: 1mm2 ~ 2.5mm2
Approx. Dimensions of the panel (W×H×D)400×360×104mm
Approx. weight (without battery)3.7kg
Operating conditionsTemperature range: -5°C~ 45°C; Max relative humidity: 95% (40°C ± 2°C, no condensation)


image.png

If you need any help, please do not hesitate to contact us by Email, we are sure that you will get our response as soon as possible.


Headquarter in Shenzhen


Tel: +86 755 2690 9106


Fax: 86 755 8622 6969


E-mail:sales@sz-sanjiang.com


Add: 3F, Guangcai Xin Tian Di Building, Nanshan Road, Nanshan District, Shenzhen, 518054, P.R.China


Copyright ©SHENZHEN HTI SANJIANG ELECTRONICS CO., LTD. | Legal notice