GET A QUOTE

Addressable(Multi)

Output module

KZ-953E

Product features

Built-in standalone CPU, quick calculating speed.

Non-polarity two-wire bus to make wiring easy and avoid mistakes.

Connect conventional detector, manual call point or fire hydrant button, and deliver the alarm signal to the controller.

Read more detail
CCCF.png

The KZ-953E output module (KZ-953E module for short) is used with a fire alarm control system. It is mainly used for the output control of fire linkage equipment (such as alarm bells).

Technical Parameters:
Operating environmentIndoors, temperature -10℃~+50℃,relative humidity ≤95%(40℃±2℃ without condensation)
Operating voltageBus24V,DC24V±20%
Operating currentMonitoring status:<600uA, action status:<10mA  
Operating indicatorstatus indicated light blinks when polling, keeps on when action.
Mode of connectionfour-wire bus: signal cable±power cable
Termination load4.7k impedance
MountingWall-mount/module case
CodingSoft addressing