Fire Alarm System (EN54)

I/O module

A9056T

Product features

LPCB and CPR approval.

2 LED indicators (Monitor/Output).

Built in terminal resistor.

Normally open/close contact signal is selected by jumper.

Read more detail
  • The A9056T I/O module (A9056T for short) is used with SEC3002 fire alarm control panel. It is mainly used to realize an output control for fire linkage equipment (such as smoke dampers, blow valves and fire dampers) and receive the feedback signals of the fire linkage equipment so that a judgment on whether or not the fire linkage equipment is operating normally can be done.

Technical Parameters:
Executive standardEN54-18
Operation voltageloop DC24V (non-polarity);power DC24V(non-polarity)
Static currentloop current<0.8mA; power current<2mA
Action currentloop current<5mA; power current<15mA
Capacity of the output control contact<2A@DC30V
Operating indicatorThe inspecting indicator blinks once about every 12 seconds in the inspection status or remain lit in the output status; the input indicator will remain lit in the feedback status
Operating environmentIndoors, Temperature: -10℃ ~ 55℃; RH: ≤95% (40 ℃±2℃, non condensing)
Dimension86×86×41(mm, With base)
Weightabout 148g(With base) 


image.png