Fire Alarm System

Manual call point

J-SAP-M-962E

Product features

It can realize complete electronic coding and in situ rewriting with help of a coder. 

Designed with an upper cover and a lower cover, it can be installed, debugged and maintained conveniently. 

It is designed with a two-wire fire telephone jack and is therefore more applicable to engineering application. 

Designed with passive output contacts, it can control other external equipment directly through an intermediate relay. 

The pressing sheet on the manual fire call point will not get crushed after it is pressed, but can be reset by a special tool, so it can be used repeatedly.

Read more detail
CCCF.png
  • The J-SAP-M-960E manual fire call points is mainly designed to be used with an intelligent two-bus control system. If it is pressed after a fire is manually confirmed, an alarm signal may be sent to a fire alarm control system which will, after receiving the alarm signal, display the coded address and the equipment status of the manual fire call points. When the manual fire call points is operating normally, the red indicator will blink; when there is a fire alarm, it will remain lit. The manual fire call points supports electronic coding and has a built-in fire telephone jack and a PHONE indicator, making its engineering application convenient.

Technical Parameters:


Executive standardGB19880-2005
Operating voltageDC24V (pulse width modulation)
Working current<300uA (in the monitoring status); <2mA (in the action status)
Output contactNormally open contact; capacity: 0.1A/30VDC
WeightAbout 112g
Wiring methodnonpolar two-bus system (L1, L2)
Operating environmentIndoor, temperature: -10℃~+50℃; relative humidity: ≤95% (40℃±2℃, without condensation)
Coding methodIt can realize online coding with the help of a coder and without the necessity of disassembling the bus (however, the equipment must be powered off). Address codes 1 to 324 are available for selection
Telephone jackTwo-wire fire telephone jack (equipped with a standard Ф6.3 single-track audio connector).
Starting partA plastic pressing sheet that may be used repeatedly. It can be manually reset with a special tool after being pressed.
Starting modePress the pressing sheet manually
IndicatorThe red ALARM indicator will blink in the inspection status or remain lit in the alarm status; the PHONE indicator will blink when a fire telephone loop is connected, otherwise it will be out.
Matched host machine9000 series fire alarm control system (such as JB-QGL-9000 or JB-QBL-MN/300)



If you need any help, please do not hesitate to contact us by Email, we are sure that you will get our response as soon as possible.


Headquarter in Shenzhen


Tel: +86 755 2690 9106


Fax: 86 755 8622 6969


E-mail: sales@fhsjdz.com


Add: 3F, Guangcai Xin Tian Di Building, Nanshan Road, Nanshan District, Shenzhen, 518054, P.R.China


Copyright ©SHENZHEN HTI SANJIANG ELECTRONICS CO., LTD. | Legal notice