JK-952E

Product features

Built-in standalone CPU, quick calculating speed.

Non-polarity two-wire bus to make wiring easy and avoid mistakes.

Connect conventional detector, manual call point or fire hydrant button, and deliver the alarm signal to the controller.

Read more detail
CCCF.png

The JK-952E input module (JK-952E module for short) is used with a two-bus fire alarm control system. It can be connected with a JTY-GD-930KE photoelectric smoke detector, a JTW-ZD-920KE heat fire detector, a J-SAP-M-960KE manual fire alarm button, a J-SAP-M-961KE hydrant button and some other equipment. After the said equipment starts to operate, the alarm signal output will be sent by the JK-952E module to the fire alarm control system through a signal bus to give a fire alarm.

Technical Parameters:
Operating environmentIndoors, temperature -10℃~+50℃,relative humidity ≤95%(40℃±2℃ without condensation)
Operating voltagebus24V,DC24V±20%
Operating currentMonitoring status:<500uA, action status:<2mA
Operating indicatorBlinks when polling, and keeps on when alarming
Four-wire bussignal cable±power cable
Termination load4.7k impedance
MountingWall-mount/module case
CodingSoft addressing